Appendix D: Specifications
49
APPENDIX D: SPECIFICATIONS
ALARM NOTIFICATION METHODS:
• E-Mail, Text Message, SNMP Trap
• 8 Alarm escalation levels
• Comprehensive scheduling per input, user, and
alarm destination
DESTINATIONS:
• 8 Programmable User Profiles
• 4 Programmable destinations per profile
• Alarms can be assigned to specific User Profiles
COMMUNICATION TYPES:
• E-Mail – SMTP
• Text Messages via SMTP
• Web page – HTTP
• SNMP – MIB with Traps, GET, GETNEXT, and
SET
• MODBUS®/TCP Slave Conformance Class 0
and 1
SENSORS:
• Up to 30 Wireless Sensors
• Dry Contact - Normally Open /Normally
Closed
• Temperature - 2.8K Thermistor
• Water detection
• Humidity
• Power Failure
• 4-20mA Current Loop
• 12-Bit Resolution
CERTIFICATION STANDARDS:
• FCC Part 15 – Class B Compliant Data logging
• 32,000 Samples (all samples include data, date,
and time)
• 1 second to 100 hours sampling rate, variable
rate per sensor
• User programmable sensor selection
• Battery
• Power Supply
COMMUNICATION PORTS:
• Ethernet 10/100Base–T
LOCAL INDICATORS:
• 80 Character lighted LCD
• Ethernet link and Activity LEDs
POWER REQUIREMENTS:
• External transformer 120VAC 60Hz
input/9VDC Output
• Rechargeable Battery Backup (included)
WIRELESS TECHNOLOGY:
• 2.4GHz/ISM
OPERATING CONDITIONS:
• 0-50°C (32–122°F)
• 0-90% RH, non–condensing
PHYSICAL PROPERTIES:
• 7.6” x 5.1” x 2.0” (19cm x 13cm x 5cm)
• 2.5 lbs (1.3kg)
Comentarios a estos manuales